Salmonsmith, Jacob;
Ducci, Andrea;
Guo, Liwei;
Torii, Ryo;
Balachandran, Ramanarayanan;
Houlihan, Catherine;
Epstein, Ruth;
... Lovat, Laurence B; + view all
(2025)
The influence of mechanical ventilation and portable air cleaners upon aerosol spread in a hospital outpatients clinic.
Aerosol Science and Technology
10.1080/02786826.2024.2446587.
(In press).
Preview |
Text
Lovat_The influence of mechanical ventilation and portable air cleaners upon aerosol spread in a hospital outpatients clinic.pdf Download (1MB) | Preview |
Abstract
The SARS-CoV-2 global pandemic has highlighted the risk of nosocomial infections of airborne viruses to patient populations around the world. Increased use of mechanical ventilation and portable air cleaners (PACs) have been suggested as methods to mitigate this risk, but the introduction of new air flows to indoor areas can have complex and potentially unforeseen consequences. We used particle counters to investigate the effect of using built-in mechanical ventilation and/or PACs in a typical hospital outpatients’ clinic upon the spread of aerosols produced by an aerosol generator. A variety of scenarios was investigated, examining particle movement to a neighboring room, throughout the whole clinic, and from one room to another at the far side of the clinic. Whilst both built-in ventilation and PACs may reduce particle migration in some scenarios by up to 96%, use of the same PACs may lead to unexpectedly increased aerosol migration of 29% between neighboring rooms, and use of built-in supply ventilation may increase aerosol migration across the clinic by up to 5.5 times. These increases are most likely due to the introduction of air flows from the outlets of these devices, providing aerosols with enough momentum to traverse the distance between relatively remote locations or creating recirculation regions that pull aerosols out of one room and push them into another. Accordingly, in order to effectively deploy these useful mitigations to their full potential and not simply displace the risk of nosocomial infection, careful consideration of placement and resultant air flow dynamics is required.
| Type: | Article |
|---|---|
| Title: | The influence of mechanical ventilation and portable air cleaners upon aerosol spread in a hospital outpatients clinic |
| Open access status: | An open access version is available from UCL Discovery |
| DOI: | 10.1080/02786826.2024.2446587 |
| Publisher version: | https://doi.org/10.1080/02786826.2024.2446587 |
| Language: | English |
| Additional information: | © 2025 The Author(s). Published with license by Taylor & Francis Group, LLC This is an Open Access article distributed under the terms of the Creative Commons Attribution-NonCommercial-NoDerivatives License (http://creativecommons.org/licenses/by-nc-nd/4.0/), which permits non-commercial re-use, distribution, and reproduction in any medium, provided the original work is properly cited, and is not altered, transformed, or built upon in any way. The terms on which this article has been published allow the posting of the Accepted Manuscript in a repository by the author(s) or with their consent. |
| Keywords: | Science & Technology, Technology, Life Sciences & Biomedicine, Physical Sciences, Engineering, Chemical, Engineering, Mechanical, Environmental Sciences, Meteorology & Atmospheric Sciences, Engineering, Environmental Sciences & Ecology, Jonathan P. Reid |
| UCL classification: | UCL UCL > Provost and Vice Provost Offices > School of Life and Medical Sciences UCL > Provost and Vice Provost Offices > UCL BEAMS UCL > Provost and Vice Provost Offices > School of Life and Medical Sciences > Faculty of Medical Sciences UCL > Provost and Vice Provost Offices > School of Life and Medical Sciences > Faculty of Medical Sciences > Div of Infection and Immunity UCL > Provost and Vice Provost Offices > School of Life and Medical Sciences > Faculty of Medical Sciences > Div of Surgery and Interventional Sci UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of Engineering Science > Dept of Mechanical Engineering UCL > Provost and Vice Provost Offices > School of Life and Medical Sciences > Faculty of Medical Sciences > Div of Surgery and Interventional Sci > Department of Targeted Intervention |
| URI: | https://discovery.ucl.ac.uk/id/eprint/10208273 |