UCL Discovery
UCL home » Library Services » Electronic resources » UCL Discovery

Performance analysis of heat recovery in CO2 refrigeration systems for heating electrification in supermarkets

Li, Wenzhuo; Korolija, Ivan; Tang, Rui; Mumovic, Dejan; (2025) Performance analysis of heat recovery in CO2 refrigeration systems for heating electrification in supermarkets. Applied Energy , 384 , Article 125461. 10.1016/j.apenergy.2025.125461. Green open access

[thumbnail of 1-s2.0-S0306261925001916-main.pdf]
Preview
Text
1-s2.0-S0306261925001916-main.pdf - Published Version

Download (9MB) | Preview

Abstract

Net-zero goals require all sectors to conduct decarbonization. Supermarkets, a significant part of the retail sector, are distinctive in opportunity to utilize heat recovery from CO2 refrigeration systems for heating load provision in attempt to electrify heating by eliminating gas consumption. This requires reliable computational models to comprehensively evaluate and analyze the heat recovery potential and the performance of different strategies before implementation. Additionally, the impact of supermarket heating electrification on electricity load variation, which would impact the connected systems and electric networks, needs to be quantified and included as a heat recovery evaluation criterion. This study, therefore, leverages a high-fidelity CO2 refrigeration system model to analyze the heat recovery performance of CO2 systems for heating electrification in a UK supermarket. Different heat recovery strategies are evaluated by energy performance, economic performance, a mismatch between recoverable heat and heating load, and the impact on electricity load variation. Results show that the instantaneous gas requirements for heating was reduced by at least 47 % using CO2 system heat recovery, with minor modifications on the default operation, up to being eliminated when the system is operated to maximize recoverable heat. Depending on the heat recovery strategies adopted, the electricity peak was shifted from midday to early-morning and summer to winter, and average and peak loads can be increased significantly. Among tested heat recovery strategies, increasing a condensing pressure to 90 bar when possible is overall the best strategy to balance low electricity consumption and costs, effective recoverable heat utilization and flat load profiles.

Type: Article
Title: Performance analysis of heat recovery in CO2 refrigeration systems for heating electrification in supermarkets
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.apenergy.2025.125461
Publisher version: https://doi.org/10.1016/j.apenergy.2025.125461
Language: English
Additional information: © 2025 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
Keywords: Food retail, R744 refrigeration system, Heating decarbonization, Heat pump, Electric load management
UCL classification: UCL
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment > Bartlett School Env, Energy and Resources
URI: https://discovery.ucl.ac.uk/id/eprint/10204247
Downloads since deposit
1Download
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item