Modeling temperature distribution and power consumption in IT server enclosures with row-based cooling architectures

Moazamigoodarzi, Hosein; Gupta, Rohit; Pal, Souvik; Tsai, Peiying Jennifer; Ghosh, Suvojit; Puri, Ishwar K; (2020) Modeling temperature distribution and power consumption in IT server enclosures with row-based cooling architectures. Applied Energy , 261 , Article 114355. 10.1016/j.apenergy.2019.114355. Green open access

[thumbnail of Gupta_extracted_Gupta_MoazamigoodarziandGuptaetal.-AppliedEnergy2020-114355.pdf]
Preview
Text
Gupta_extracted_Gupta_MoazamigoodarziandGuptaetal.-AppliedEnergy2020-114355.pdf

Download (2MB) | Preview

Abstract

Traditional data center cooling methods cannot yet control cooling airflows and temperatures on demand, creating an intrinsic inefficiency. A recent solution places row-based cooling unit adjacent to servers and places the entire assembly within an enclosure, which improves airflow distribution and provides rapid real-time control. This is, in particular attractive for micro-data centers where traditional room-based cooling is less energy efficient. Spatiotemporal predictions of temperatures are required to control and optimize data center performance as the system configuration, and other parameters are varied. Current methods, such as proper orthogonal decomposition, machine learning, and heuristic models are inapplicable in practice because they require a prohibitively large number of a priori simulations or experiments to generate training datasets. We provide an alternative a computationally inexpensive training-free model for enclosed micro-data centers that are integrated with in-row cooling units that requires no a priori training. The model determines the air flowrate within each zone based on a mechanical resistance circuit analysis. These flowrates are then introduced into a zonal energy balance to predict the temperature of each zone. The methodology is validated with experimental measurements and coupled with a power consumption calculation. Its applicability is demonstrated by evaluating the influence of various system factors, such as IT server configurations, cooling unit air, and water flowrates and the numbers of cooling units, on the temperature distributions, and total cooling power consumption. The method can improve micro-data centers control and help to optimize the design of any data center with a row-based cooling system.

Type: Article
Title: Modeling temperature distribution and power consumption in IT server enclosures with row-based cooling architectures
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.apenergy.2019.114355
Publisher version: https://doi.org/10.1016/j.apenergy.2019.114355
Language: English
Additional information: This version is the author accepted manuscript. For information on re-use, please refer to the publisher’s terms and conditions.
Keywords: In-row cooling unit, Temperature prediction, Zonal method, Mechanical resistance, Energy balance, Data center, Energy optimization
UCL classification: UCL
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of Engineering Science
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of Engineering Science > Dept of Mechanical Engineering
URI: https://discovery.ucl.ac.uk/id/eprint/10161275
Downloads since deposit
122Downloads
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item