Experimental and numerical study on the heat transfer performance of the radiant floor heating condenser with composite phase change material

Jiang, Tingting; Zheng, Chenxiao; You, Shijun; Zhang, Huan; Wu, Zhenjing; Wang, Yaran; Wei, Shen; (2022) Experimental and numerical study on the heat transfer performance of the radiant floor heating condenser with composite phase change material. Applied Thermal Engineering , 213 , Article 118749. 10.1016/j.applthermaleng.2022.118749. Green open access

[thumbnail of 1-s2.0-S1359431122006925-main.pdf]
Preview
Text
1-s2.0-S1359431122006925-main.pdf - Accepted Version

Download (1MB) | Preview

Abstract

Traditional hot-water ASHP systems have disadvantage of low energy efficiency due to the requirement of secondary heat exchange. To maintain the stability of indoor air temperature during defrosting, the existing ASHP systems adopt heat exchanger to store heat, which increases the system complexity. To overcome these obstacles, a novel ASHP system integrated with radiant floor heating condenser (RFHC) is proposed, which uses refrigerant as working fluid to exchange heat with indoor environment directly. In addition, the composite phase change material (CPCM) is added in the RFHC for heat storage. Experiments are conducted and results show that compared with traditional ASHP systems, the proposed system has higher energy efficiency and can reduce indoor air temperature fluctuation under defrosting condition. A detailed numerical model of the RFHC is established and validated with the experimental data, and then the impacts of the operating and structural parameters on the heat transfer performance of the RFHC system are investigated. Results show that under the indoor air temperature of test room keeps at 18.0 oC, the optimal operating condition of this system is the condensing temperature with 38.0 oC and the refrigerant mass flow rate with 3.8 kg· h-1. The optimal structural scheme of the RFHC is the copper pipe spacing with 0.25 m and the length of copper pipe with 12.0 m.

Type: Article
Title: Experimental and numerical study on the heat transfer performance of the radiant floor heating condenser with composite phase change material
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.applthermaleng.2022.118749
Publisher version: https://doi.org/10.1016/j.applthermaleng.2022.1187...
Language: English
Additional information: This version is the author accepted manuscript. For information on re-use, please refer to the publisher’s terms and conditions.
Keywords: radiant floor heating condenser, composite phase change material, numerical modelheat transfer performance, structural scheme
UCL classification: UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL
URI: https://discovery.ucl.ac.uk/id/eprint/10149941
Downloads since deposit
17Downloads
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item