A dual-objective trade-off approach to decide the optimum design parameters for internal cooling load calculation

Ding, Yan; Li, Junchu; Liu, Kuixing; Wei, Shen; Chen, Wanyue; Han, Shuxue; (2022) A dual-objective trade-off approach to decide the optimum design parameters for internal cooling load calculation. Energy and Buildings , 269 , Article 112230. 10.1016/j.enbuild.2022.112230. Green open access

[thumbnail of 1-s2.0-S0378778822004017-main.pdf]
Preview
Text
1-s2.0-S0378778822004017-main.pdf - Accepted Version

Download (2MB) | Preview

Abstract

The building design cooling load is the basis of sizing the air-conditioning equipment, but the extreme values are always used as the referenced design parameters for occupants, lighting and equipment respectively without considering the relationship between the internal load sources which will result in an oversized equipment. Based on the measured data in existing buildings, the Copula function is used to explore the joint occurrence probability of the internal disturbances. In view of the deviation of the calculated cooling load from the extreme cooling load, the unguaranteed rate is established. Aiming to balance the maximum joint probability and the minimum unguaranteed rate, a dual-objective trade-off approach with the genetic algorithm and TOPSIS method is proposed to seek the optimum solution from the Pareto Fronts to provide references for internal load design parameters. The results show that there is a big deviation between the design values and trade-off results, especially the recommended values of lighting power density in the design standards are at least 26% higher than the trade-off results. And the energy consumption for internal disturbances can be at least reduced by 12.1% using the trade-off approach.

Type: Article
Title: A dual-objective trade-off approach to decide the optimum design parameters for internal cooling load calculation
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.enbuild.2022.112230
Publisher version: https://doi.org/10.1016/j.enbuild.2022.112230
Language: English
Additional information: This version is the author accepted manuscript. For information on re-use, please refer to the publisher’s terms and conditions.
Keywords: internal loads, trade-off approach, unguaranteed rate, internal disturbances, joint probability distribution
UCL classification: UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL
URI: https://discovery.ucl.ac.uk/id/eprint/10149937
Downloads since deposit
24Downloads
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item