Indoor air quality (IAQ) in naturally-ventilated primary schools in the UK: Occupant-related factors

Korsavi, SS; Montazami, A; Mumovic, D; (2020) Indoor air quality (IAQ) in naturally-ventilated primary schools in the UK: Occupant-related factors. Building and Environment , 180 , Article 106992. 10.1016/j.buildenv.2020.106992. Green open access

[thumbnail of Mumovic_Indoor Air Quality in Naturally ventilated Primary Schools in the UK.pdf]
Preview
Text
Mumovic_Indoor Air Quality in Naturally ventilated Primary Schools in the UK.pdf - Accepted Version

Download (1MB) | Preview

Abstract

Indoor Air Quality (IAQ) is affected by Context, Occupant and Building (COB) related factors. This paper evaluates IAQ as a function of occupant-related factors including occupants' Adaptive Behaviours (ABs), occupancy patterns, occupant's CO2 generation rates and occupancy density. This study observed occupant-related factors of 805 children in 29 naturally-ventilated (NV) classrooms in UK primary schools during Non-Heating and Heating seasons. Occupant-related factors affecting IAQ include occupants' adaptive behaviours, occupancy patterns, occupants' CO2 generation rate and occupancy densities. Results of this study suggest that a classroom with high potentials for natural ventilation does not necessarily provide adequate IAQ, however, occupants’ good practice of ABs is also required. Average occupancy densities to have CO2 levels of 1000 ± 50 ppm are suggested to be 2.3 ± 0.05m2/p and 7.6 ± 0.25 m3/p. These values correspond to the classroom area of 62.1 ± 1.35 m2 and volume of 205.2 ± 6.75 m3 with a height of 3.3 m. Mean CO2 level is maintained below 900 ppm when all occupant-related factors are in the favour of IAQ, however, it exceeds 1300 ppm when none of the occupant-related factors are in favour of IAQ. It is shown that 17% of CO2 variations are explained by open area (m2), 14% by occupants' generation rates (cm3/s) and 11% by occupancy density (m3/p). IAQ is mostly affected by occupants’ adaptive behaviours than other occupant-related factors in naturally-ventilated classrooms.

Type: Article
Title: Indoor air quality (IAQ) in naturally-ventilated primary schools in the UK: Occupant-related factors
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.buildenv.2020.106992
Publisher version: https://doi.org/10.1016/j.buildenv.2020.106992
Language: English
Additional information: This version is the author accepted manuscript. For information on re-use, please refer to the publisher’s terms and conditions.
Keywords: Indoor Air Quality (IAQ), CO2 levels, Occupants, Adaptive Behaviours, Occupancy Density (OD), Primary Schools
UCL classification: UCL
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment > Bartlett School Env, Energy and Resources
URI: https://discovery.ucl.ac.uk/id/eprint/10108202
Downloads since deposit
293Downloads
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item