Performance of a natural ventilation system with heat recovery in UK classrooms: An experimental study

Stamp, SF; Dorizas, PV; Mumovic, D; Yan, K; Makris-Makridis, D; Lipinski, T; (2018) Performance of a natural ventilation system with heat recovery in UK classrooms: An experimental study. Energy and Buildings , 179 pp. 278-291. 10.1016/j.enbuild.2018.09.005. Green open access

[thumbnail of 1-s2.0-S0378778818303475-main.pdf]
Preview
Text
1-s2.0-S0378778818303475-main.pdf - Accepted Version

Download (1MB) | Preview

Abstract

This paper presents the ventilation performance of a Passive Ventilation System with Heat Recovery (PVHR) based on in-situ monitoring in a primary school in London. The study involves long-term (15-month) monitoring of temperature, relative humidity and Carbon dioxide (CO2) concentrations in both the classrooms and the outdoor environment. In addition, short term (1&2 week) observational monitoring was performed in two classrooms at ventilation system level and classroom level, during both the heating and non-heating seasons. Temperatures and air velocities were measured within the PVHR system while instances of window opening and the number of students were noted in daily diaries. Air permeability and infiltration measurements were performed to characterise the spaces. Time-varying ventilation rates were estimated through a form of continuity equation considering CO2 generation rates by occupants. Preliminary results show that the operation of the ventilation system is more sensitive to changes in wind speed and direction than to buoyancy. When negative pressure was observed on the classrooms’ facades the ventilation system was supplying two to three times more air in comparison to instances when positive pressures were observed. The assessment of the ventilation performance of such natural ventilation systems depending solely on wind and buoyancy is complicated as they are dynamic systems that constantly balancing with the surrounding conditions, and the operation is highly correlated to the airtightness of the building's envelope.

Type: Article
Title: Performance of a natural ventilation system with heat recovery in UK classrooms: An experimental study
Open access status: An open access version is available from UCL Discovery
DOI: 10.1016/j.enbuild.2018.09.005
Publisher version: https://doi.org/10.1016/j.enbuild.2018.09.005
Language: English
Additional information: This version is the author accepted manuscript. For information on re-use, please refer to the publisher’s terms and conditions.
Keywords: Natural ventilationIndoor, Air Quality (IAQ), Air tightness, Schools
UCL classification: UCL
UCL > Provost and Vice Provost Offices > UCL BEAMS
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment
UCL > Provost and Vice Provost Offices > UCL BEAMS > Faculty of the Built Environment > Bartlett School Env, Energy and Resources
URI: https://discovery.ucl.ac.uk/id/eprint/10057141
Downloads since deposit
190Downloads
Download activity - last month
Download activity - last 12 months
Downloads by country - last 12 months

Archive Staff Only

View Item View Item